Grounding Measurement Applied to a 13.8 kV Substation in Manaus - Amazonas 319 96

Authors

  • Carlos Gilmar França dos Santos Author
    • Livia da Silva Oliveira Author
      • David Barbosa de Alencar ITEGAM Author
        • Francisco Carlos Tavares Amorim Author

          DOI:

          https://doi.org/10.31686/ijier.vol7.iss10.1804

          Keywords:

          electricity, electrical grounding, sheltered substation

          Abstract

          The aim of this study is to show a practical grounding measurement method for 13.8 kV step-down sheltered substation to serve as support material for use in the area.If required, an analytical comparative method for groundmeasurementthroughtheterrometer measurement equipment in the ground measurement process of a step down 13.8 kV substation with its equipment,comparing the data obtained referring to the commonly used methods, thus identifying among the most efficient grounding processes.The development of this study was based on the measurement of electrical grounding with a terrometer in a factory located in the city of Manaus. The procedure used was to perform resistance measurements, to record through measurements and images all the system measurements, to compare the values through Conventional measurement method, with electrical ground ohmic resistance meter, displaying tables and graphs to demonstrate whether the electrical grounding of the entire system would be at adequate levels.

          Downloads

          Published

          2019-10-01

          How to Cite

          França dos Santos, C. G., da Silva Oliveira, L., Barbosa de Alencar, D., & Tavares Amorim, F. C. (2019). Grounding Measurement Applied to a 13.8 kV Substation in Manaus - Amazonas. International Journal for Innovation Education and Research, 7(10), 576-584. https://doi.org/10.31686/ijier.vol7.iss10.1804